| Specifications | 1030KW 210 Rack Space | 
| Model | ANTSPACE HK3 V6 | 
| Dimensions (L*W*H) (mm) | 6058*2438*2896 | 
| Miner Capacity | 210 units -S19 Hyd. & S21 Hyd. Series miner | 
| Container Certification | China Classification Society Certification | 
| Safety Certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No. 14-18 ANSI/ISO 12100:2012 IEC 60204 Ed 5.1 2009  | 
| Operating Power(kW) | 1047~1050 | 
| PUE(Power Usage Effectiveness) | 1.022(Excluding cooling tower)/1.032(Including cooling tower) | 
| Input Voltage and Frequency | 400V±5% 50/60Hz | 
| Detailed Characteristics | |
| Shipping Weight(T) | 8 | 
| Operating Weight (T) | 12 | 
| Main Switch of Power Distribution Cabinets(A) | 1200*2 | 
| Rated Current(A) | A:952; B:866 | 
| Rated Current per Miner(A) | 10 | 
| Inlet Cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements: L1 single core cable 600kcMil(300mm²)x4 L2 single core cable 600kcMil(300mm²)x4 L3 single core cable 600kcMil(300mm²)x4 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2  | 
| Connection Interface(Cooling Tower) | DN100(ISO2852 PN16) | 
| Connection Interface(Plate Heat Exchage Interface) | DN100(GB/T 9122-2010 PN16 DN100) | 
| Flow Rate(m³/h) | >85 | 
| Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 | 